Homepage | Add to Favorites | Chinese  |  English     
 
  Home | About Us | News Center | Product Center | Quality Assurance | Service Commitment | Download | Contact Us  
  Products  
Fiberglass Insulation
Live Line Tools
 FRP hot Sticks
 Insulation Ladders
 HUBBELL Distribution Connectors
Insulator
 Composite Insulator
 Suspension & Tension Insulator
 Line Post Insulator
 Station & Switch Post Insulator
 Railway Insulator
 Stay Insulator
 Hollow Insulator
 ESP insulator
 Insulator Fitting
Surge Arrester
 Polymer Arrester
Fuse Cut out
Composite Bushing
 Capacitance Wall Bushing
 Capacitance Transformer Bushing
 Capacitance Bushing For The Railwa
 Capacitance Bushing For Wind Power
 Capacitance Oil/oil Bushing
 Capacitance Oil/SF6 Bushing
Service Online
        
Tel:00869132128099
Fax:00869132128099
Mob:008618191816622
Email:sale@tidpower.com
Website:http://www.tidpower.com
Polymer Arrester
Polymer Surge arreter 132 kV/10kA
Posted:2016-12-09 | Browse: 835 【Close this page

Polymer Surge arreter

Polymer Surge arreter 132 kV/10kA


1.Product Type:

Surge arrester can be divided into many types according to its application as below:

Distribution type,power station type,protecting capacitor type,transformer neutral point type ,protecting motor type,electrified railway type,line type.etc.

Line type surge arrester can be divided into series spacing type and without spacing type and in series spacing type can be divided into supporting spacing and sure air spacing type.

2.Main Product Features:

2.1It has a series of outstanding features such as good protection performance,high circulating capacity ,less reaction time,smooth steep-wave characteristic.

2.2 Excellent silicon rubber material is used in composite housing,possessing good anti-tracking and ageing-resistant performance as well as good hydrophobicity ,ion transferring and high pollution proof.

2.3 Special technique and internal structure are used in composite housing surge arrester,possessing higher technical strength and good explosion-proof performance.

3.Service Conditions:

3.1 Ambient Temperature:≥ - 40 ℃≤ + 50 ℃ ;

3.2 Altitude: ≤ 1000m;

3.3 Frequency ≥ 48 Hz ≤ + 50 Hz;

3.4 Power Frequency Voltage exerted long-time on surge arrester shall not exceeds continuous operation voltage;

3.5 Earthquake intensity is not more than 7 grades;

3.6 Wind speed is not more than 35mm/s;

Usage under exceptional conditions shall be negotiated by both parties.

4.drawing:



5 Technical Character:

5.1 Type designation : Polymer type

5.2 Applicable standard :IEC 60099-4

5.3 Class (outdoor/indoor):Outdoor

5.4 Ambient temperature : -40 to +55 °c

5.5 Max. design altitude :2500m

5.6 Pollution level :Very heavy

5.7 Design siesmic acceleration :0.35

5.8 max. permissible wind velocity :50 m/s

5.9 Relative humidity 90%

5.10 Solar radiation 1.1 w/m²

5.11 Nominal system voltage131kV

5.12 Max. system voltage :145kV

5.13 Rated voltage (Ur) :120

5.14 Continuous operating voltage (Uc):96 KVrms

5.15 Nominal discharge current (In) : 10 KApeak

5.16 Line discharge class (LDC) : 3

5.17 Energy absorption capability (2 Impulse) :≥9.5 Kj/KV(Ur)

5.18 High current impulse withstand :100KApeak

5.19 Steep current impulse10KA (1/20 µs):≤310 KVpeak

5.20 Steep current impulse 20KA (1/20 µs):≤345KVpeak

5.21 lightning impulse residual voltages (8/20 µs): 5 KA ≤282KV peak ,10 KA ≤294KV peak,20 KA≤328 KV peak

5.22 Switching impulse residual voltages (30/60 µs): 125(A) ≤229 KV peak ; 250(A)≤234 KV peak 500(A) ≤241KV peak; 1000(A) ≤248 KV peak; 2000(A) ≤260KV peak

5.23Temporary overvoltage withstand (Prestressed) 1 Second 138 KVrms ; 10 Second 132KVrms ; 100 Second126KVrms

5.24Max. internal partial discharge at 1.05Uc <10 pc

5.25 Power-frequency withstand voltage : Dry520kV ; Wet 419 kV

5.26 lightning impulse withstand voltage: Dry 860kV; Wet700 kV


5.27Rated frequency: 50-60 Hz.

5.28Reference voltage of 1mA DC (U1mA DC) 1mA ≥170 KVDC

5.29Diameter : φ210/φ174 mm

5.30Height : 1686 mm

5.31 Total weight of arrester :42kg

5.32Total creepage distance of arrester :4850mm

5.33 Total arc distance of arrester1400mm

5.34 Specified Short term Load (SSL) :4700 N.m

5.35 Specified Long term Load (SLL) : 1880 N.m

5.36Mean value of Breaking Load (MBL): 6000N.m

5.37Torsional strength : 250N.m

5.38 Tensile strength: 2KN



Hot Line:0086-18191816622 Website:Http://www.tidpower.com