11kv-69kV Dead End Polymer Insulator
1.1hgh mechanical strength;
1.2Good performance of hydrophobicity and anti-pollution;
1.3 Excellent electrical Performance;
1.4 Small volume and light weight.
2.TID polymer Insulator Character:
2.1 We adopt the advanced injection producing technology for housing and the design of the shed adopt unique
aerodynamics principle.
2.2 We use HTV silicone rubber which hydrophobicity can reach to HC1 level and thickness of the housing is
more than 3mm .
2.3 We use ECR rod which is high acid resistant as the core.
2.4 We use hot dip Galvanizing steel fitting ,the thickness of the zinc more than 86μm.
2.5 We adopt the advance fitting crimping producing technology .
2.6 We adopt the unique notch design of the sealing of metal fitting, all the notch thickness keep the same which avoid the sharp end discharge.
2.7 We use HTV instead of the RTV seal the interface between the fitting and rod.
3.The Technical Character
Part Number
|
Rated
Voltage
|
Tensile
Load
|
Section
Length
|
Creepage
distance
|
Power Frequency
Withstand Voltage
|
Lighting Impulse
Withstand Voltage
|
Applied
Standard
|
Dry
|
Wet
|
Pos..
|
FXB-15/70
|
15
|
70
|
343
|
365
|
90
|
65
|
140
|
ANSIC29
|
FXB-28/70
|
24
|
70
|
445
|
550
|
130
|
100
|
190
|
FXB-3570
|
33
|
70
|
541
|
730
|
145
|
130
|
250
|
FXB-46/70
|
46
|
70
|
590
|
900
|
180
|
145
|
280
|
FXB-69/70
|
69
|
70
|
750
|
190
|
220
|
185
|
360
|
|